网站公告-NOTICE
联系我们
济南航丰实业有限公司

电话:15168870138
联系人:庞经理

网址:http://www.sdhangfeng.com  

厂址: 德州市禹城市莒镇产业园26栋

经销商地址:天桥区建华五金市场东区5-1  

鲁ICP备09095923号-1

新闻资讯

当前位置:首页 / 新闻资讯

讲解一下槽式电缆桥架接地要点

  槽式电缆桥架接地要点:
  Groove type cable tray grounding points:槽式电缆桥架
  1、桥架系统应具有可靠的电气连接并接地(只对金属桥架)。
  1, the bridge system should have reliable electrical connection and grounding (only for metal bridge).
  2、当允许利用桥架系统构成接地干线回路时应符合下列要求。桥架端部之间连接电阻应不大于0.00033欧姆,接地孔应绝缘涂层。在1KV及以下中性点直接接地系统中,受电设备的接地与系统中性线接地相连。装有处动切断供电装轩时,桥架的级长方向金属横截面积应不小于规定值。
  2, when allowed to use bridge system grounding main circuit, shall meet the following requirements. Connection between the bridge end resistance should be no greater than 0.00033 ohms, grounding insulation coating shall be removed. In the neutral point grounding system directly 1 kv and below, from electrical equipment grounding connected to the neutral grounding system. Move to cut off the power supply is installed with a place porch, prefect direction of bridge metallic cross-sectional area shall be not less than the specified value.
  3、沿桥架全长另敷设接地干线时,每段(包括非直线段)桥架应少有一点与接地干线可靠连接。
  3, along the bridge span laying grounding line, other (including the straight segment) for each bridge should be at least a little and reliable grounding line connection.
  4、对于振动场所,在接地部位的连接处应装置弹簧圈。
  4, for vibration place, in the joint of ground parts should be spring coil.
  我们已做好准备,以全新的姿态迎接新老客户,欢迎您来电咨询,洽谈,我们将继续为您把好关,服好务。
  We have prepared, with new attitude to meet new and old customers, welcome to inquire, negotiate, we will continue to put good for you, take good service.
 
qq
售前咨询热线
15168870138
售后咨询热线
13465410318