1、电缆桥架与连接板的固定:每个连接孔内都应该拧紧螺栓,螺母漏在桥架的外面 。
1. Fixation of cable tray and connecting plate: bolts should be tightened in each connecting hole, and nuts leak out of the tray.
2、槽式电缆桥架伸出建筑物墙外时,它外向的倾斜角度不得小于1/100。
2. When the trough cable tray extends out of the building wall, its outward inclination angle shall not be less than 1/100.
3、电缆桥架与用电设备的净间距不得小于0.5米,电缆桥架平行铺设时,它的净间距不得小于0.6米。
3. The net distance between the cable bridge and the electrical equipment shall not be less than 0.5 meters. When the cable bridge is laid parallel, the net distance between the cable bridge and the electrical equipment shall not be less than 0.6 meters.
4、电缆桥架应高出地面2.2米以上
4. Cable bridge should be 2.2 meters above ground level.
5、电缆桥架的顶部据顶棚的距离不得小于0.3米
5. The distance between the top of the cable bridge and the roof shall not be less than 0.3 meters.
6、电缆的填充率不应超过桥架断面的50%。
6. The filling rate of cable should not exceed 50% of the bridge section.
7、电缆桥架的支持间距一般是1.5米-2米之间
7. The support spacing of cable bridge is generally between 1.5 m and 2 m.
8、电缆的铺设倾斜角大于45度的,每隔2米固定一次。
8. If the inclination angle of cable laying is greater than 45 degrees, it shall be fixed every 2 meters.